Provides electrical protection from 500V AC to 36000V AC working voltage

  • Make in India
  • KAMFET Rubber Insulating Gloves protect the people working on live voltages or in proximity of electrical installations from electrical shocks.
  • Used for a wide range of voltages from 500 V AC upto 36000 V AC
  • Compliant with EN60903:2003, IEC60903:2014 and CE category III.
Please Select Maximum Working Voltage
Please Select Palm Size

Please connect with us

Specifications

Classification Max Working Voltage Proof Test Voltage Withstand Voltage

Max use Voltage (DC)

Class 00 500 AC 2,500 AC 5,000 AC 750 DC
Class 0 1,000 AC 5,000 AC 10,000 AC 1500 DC 
Class 1 7,500 AC 10,000 AC 20,000 AC 11250 DC
Class 2 17,000 AC 20,000 AC 30,000 AC 25500 DC
Class 3 26,500 AC 30,000 AC 40,000 AC 39750 DC
Class 4 36,000 AC 40,000 AC 50,000 AC 54000 DC

Technical Information

Parameter
Palm sizes: 7,8,9,10,11,12
Length: 280mm,360mm,410mm
Category:  Class 00  - AZC | Class 0 - 4 – RC
Passed extreme low temperature test 
Resistant to Acid, Ozone, Oil
Ergonomic design provides comfort for longer working hours
Must be used with leather over gloves for mechanical hazard protection 
Powder free 

FAQ's

  • Buying
  • Specifications
  • Installation

Q. Which gloves should I select?

For selecting gloves, find out the voltage of network/panel and select the appropriate class from the classification table provided in specifications

Q. What is the technology used for manufacturing KAMFET Electrical Insulating Gloves?

KAMFET Electrical gloves are manufactured with latest robotic latex dipping technology

Q. Why do I need to wear leather over gloves?

Rubber insulating gloves are designed for protecting against electrical shocks but not designed for mechanical hazards. To provide mechanical hazard protection like abrasion, cut, tear and puncture, wearing leather over gloves.

Q. How should I store my rubber gloves?

Rubber insulating gloves should be stored hanging in a glove bag with the fingers up, not laid flat. Leather protectors should be removed before storing. Store in a dry and cool location as specified by the manufacturer in the instruction manual. Keep the gloves away from direct sunlight or areas where ozone is generated due to motors or any other possible source.

Q. Does Electrical insulation gloves need retesting?

Yes. As per governing standards of electrical insulation gloves, the gloves need to be dielectrically retested after every six months from the date of usage. For further clarification follow the instructions provided in the instruction manual.

Certifications

IEC 60903
IEC 60903

More info. Available on request

CE certified
CE certified

More info. Available on request

EN 60903
EN 60903

More info. Available on request